Bryant NON-PROGRAMMABLE THERMOSTAT Manuel d'instructions

Naviguer en ligne ou télécharger Manuel d'instructions pour Thermostats Bryant NON-PROGRAMMABLE THERMOSTAT. Bryant NON-PROGRAMMABLE THERMOSTAT Instruction manual [fr] Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Installation Instructions
T6-- PAC, T6-- PHP,
T6--NAC, T6--NHP
PREFERREDt SERIES
AC / HP THERMOSTAT
A07045 A07044
Programmable Control Non---Programmable Control
NOTE: Read the entire instruction manual before starting the installation.
Vue de la page 0
1 2 3 4 5 6 ... 55 56

Résumé du contenu

Page 1 - Installation Instructions

Installation InstructionsT6-- PAC, T6-- PHP,T6--NAC, T6--NHPPREFERREDt SERIESAC / HP THERMOSTATA07045 A07044Programmable Control Non---Programmable Co

Page 2 - SAFETY CONSIDERATIONS

10UNIT DAMAGE HAZARDFailure to follow this caution may result in equipment damageor improper operation.Improper wiring or installation may damage AC/H

Page 3 - INTRODUCTION

11ENVIRONMENTAL HAZARDFailure to follow this caution may result in environmentaldamage.Mercury is a hazardous waste. Federal regulations require thatM

Page 4 - INSTALLATION CONSIDERATIONS

12A07225Fig. 4 -- Press Tabs to Remove BackplateA07226Fig. 5 -- Take Apart

Page 5 - Outdoor Temperature Sensor

132. Route wires through large hole in mounting base. Level mounting baseagainst wall (for aesthetic value only—Display Module need not be lev-eled fo

Page 6

146. Match and connect equipment wires to proper terminals of each connectorblock being careful not to over tighten the screws. Correct polarity mustb

Page 7 - INSTALLATION

15A07166Fig. 8 -- Secure Wir es to Terminal StripA07167Fig. 9 -- Connect Pigtail Wires to Display Module

Page 8 - AC/HP Control Location

16NOTE: The 2--wire pigtail is not intended to support the weight of the UserInterface. Do not hang the User Interface from the equipment Control Modu

Page 9 - Install AC/HP Control

1710. Find suitable indoor mounting location for Equipment Control Module,either near or on equipment. See Fig. 11.IMPORTANT NOTE: Equipment Control M

Page 10

18A07227Fig. 12 -- Standoff12. Match and connect equipment wires to proper terminals of each connectorblock being careful not to over tighten the scre

Page 11 - Two--Piece Installation

19A07218Fig. 13 -- Cover on Equipment Control Module14. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the nex

Page 12 - Fig. 5 -- Take Apart

2TABLE OF CONTENTSPAGESAFETY CONSIDERATIONS 2...INTRODUCTION 3...INSTALLAT

Page 13

20wall (for aesthetic value only -- Equipment Control Module need not beleveled for proper operation) and mark wall through 2 mounting holes.2. Drill

Page 14

215. Match and connect equipment wires to proper terminals of each connectorblock.6. Push any excess wire into wall and against Equipment Control Modu

Page 15

229. Turn on power to equipment. On power up, all display segments willlight for 5 sec. For the next 5 sec a 2--digit code appears on large displaywhi

Page 16

23Option 07 — ZoningOption 08 — Auxiliary Heat Lockout Temperature Setting (onlyavailable when heat pump is used and whenoutdoor air temperature senso

Page 17

24Option 31* — Daylight Savings Time Configuration(programmable models only)Option 32 — Furnace Heat StagingOption 33 — Single or Two--Piece Installat

Page 18

25AC model — Range: AC, H, C.HP — operates a single-- speed heat pump with a fan coil.AC — operates a single-- speed AC.H — operates a heat--only syst

Page 19 - Single--Piece Installation

26select OFF. Some auxiliary heaters require separate G signal to turn on blower. Inthis case, select On.Default is OF (off).Option 05 — Room Air Temp

Page 20

27OF (off) -- function is disabled. Auxiliary heat is allowed to operate wheneversufficient demand for heat is available.5--55_F -- Outdoor temperatur

Page 21

28programmed. Not available with non--programmable thermostats or whenthermostat is configured as non --programmable.Default is 90.Option 13 — Room Ai

Page 22

296 — The heating and cooling outputs will be energized no more than 6 times perhour. When an output is energized, it will not be energized again for

Page 23

3INTRODUCTIONBryant’s 7-- day, 5/2 --day, 1-- day programmable and non--programmablePreferredt Series Thermostat Control is a wall --mounted, low--vol

Page 24

30value between 0 and 60 will be shown in the minutes display. See OperationalInformation and Wiring Diagrams for further explanation of dry contactco

Page 25

31Option 21 — Keypad Lockout (non--programmable models only)This selection allows the installer to limit access to the keypad. Selections are OF(off),

Page 26

324 — Periods WAKE, DAY, EVE, and SLEEP are available.Default is 4.Option 26 — Minimum Cooling SetpointThis selection allows the installer to configur

Page 27

33OF (off) — The Humidifier Pad Reminder is disabled and will never bedisplayed.1-- 24 — The number o f months after which the Humidifier Pad Reminder

Page 28

34Daylight Savings Time by setting the day of the week by selecting theappropriate triangle icon next to the days of the week, the month of the year w

Page 29

35Option 99 — Reset to Factory DefaultsUse this capability to reset the stat to “out of the box” conditions. BEWARE! Allconfiguration settings, progra

Page 30 - Adjustment

36SYSTEM START--UP AND CHECKOUTThe AC/HP Control is designed with a built--in installer test capability. It allowseasy operation of equipment without

Page 31

37TO TEST FANFan button switches FAN icon between AUTO and On. While On is displayed,G output will be energized, turning fan on. Allow up to 10 sec af

Page 32

38If fixed temperatures are desired, use SCHEDULE button to turn on arrow iconnext to HOLD. This will maintain setpoints, not allowing them to change

Page 33

39Vacation (programmable models only)A vacation selection is available specifically for times where the home will notbe occupied for an extended perio

Page 34

4INSTALLATION CONSIDERATIONSPowerThis control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and Cterminals) of the low-- voltage transform

Page 35

40Cycle TimerBased on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or10 minutes. This much time must elapse from the star

Page 36 - SYSTEM START--UP AND CHECKOUT

41Thr ee--Minute Minimum on TimeIn normal operation, when a stage turns on, it will not turn off for a minimum of3 minutes. If the setpoint is changed

Page 37 - Final Settings

42Programmable Fan (programmable models only)The fan output can be programmed based on period of the day. Whenprogramming for each day and period the

Page 38

43TROUBLESHOOTINGIf the display module doesn’t power up after power is applied, check the Rc/Rhand C terminals for 24VAC. If 24VAC is present, check t

Page 39 - OPERATIONAL INFORMATION

44Table 3 – Equipment Configuration OutputsEQUIPMENT-CONFIGURATIONOPTION #1HARDWARECONFIGURATIONCOOLSTAGE1COOLSTAGE2HEATSTAGE1HEATSTAGE2HEATSTAGE3EMHE

Page 40

45WIRING DIAGRAMSDisplay moduleDisplay module wall mount Equipment Control ModuleFan CoilHeat PumpV+ V+Vg Vg O OV+V+ RVS/Heat Stage 2 O/B W2 W3 W2VgVg

Page 41 - Equipment On Indicators

46Thermostat Fan Coil Heat PumpOORVS/Heat Stage 2 O/B W2 W3 W2Heat Stage 1 W/W1 W2Compressor Y/Y2 Y YNot Used Y1Fan G G24VAC Hot Heating Rh R R24VAC H

Page 42

47Thermostat Fan CoilORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcDry Con

Page 43 - TROUBLESHOOTING

48Thermostat Fan Coil Air ConditionerORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2 Y YNot Used Y1Fan G G24VAC Hot Heating Rh R R24VAC

Page 44

49Thermostat Fan CoilORVS/Heat Stage 2 O/B W2 W3Heat Stage 1 W/W1 W2Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcDry Con

Page 45 - WIRING DIAGRAMS

5A07052Fig. 1 -- PCB Breakout JumperModelsThere are programmable and non--programmable models for all applications.They can be configured for AC or HP

Page 46

50Thermostat Furnace Air ConditionerHeat Stage 1 W/W1 WCompressor Y/Y2 Y YNot Used Y1Fan G G24VAC Hot Heating Rh R R24VAC Hot Cooling RcDry Contact 1

Page 47

51ThermostatRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Y/Y2Not Used Y1Fan G G24VAC Hot Heating Rh R24VAC Hot Cooling RcDry Contact 1 D1Dry Con

Page 48

52Thermostat Furnace Air ConditionerW2RVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1 W1Compressor Y/Y2 Y YNot Used Y1Fan G G24VAC Hot Heating Rh R R24VAC Ho

Page 49

53Single-Stage Single-StageThermostat Furnace Air ConditionerRVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1 WCompressor Low Y1Compressor High Y/Y2 Y YFan G

Page 50

54THERMOSTAT CONFIGURATION RECORDInstaller_________________________Model Number______________________________Date_________________________A. Hardware

Page 51

55E Configuration OptionsOption 01_____Equipment TypeOption 02_____Clean Filter Timer AdjustmentOption 03*_____Fahrenheit/Centigrade SelectionOption 0

Page 52

56E Configuration Options (cont)Option 21*_____Keypad LockoutOption 24*_____Programmable/Non--Programmable (programmable models only)Option 25*_____Nu

Page 53

6dedicated sensor wires may be used for its connection. Details are provided insensor instructions.Remote Indoor Temperature SensorA remote temperatur

Page 54

7INSTALLATIONCarton contains the following components. See Fig. 2 for programmable modelsor Fig. 3 for non-- programmable models.A07756Fig. 2 -- T6--P

Page 55

8A07757Fig. 3 -- T6--NAC / T6--NHP Carton Contents1. Display Module2. Stand-- off for Equipment Control Module3. Screws and pig tail4. Equipment Contr

Page 56

9AC/HP Control should NOT be mounted:S Close to a window, on an outside wall, or next to a door leading to theoutside.S Exposed to direct light or hea

Commentaires sur ces manuels

Pas de commentaire