NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage thermostat.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result
in severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which may result in enhanced installation, reliability,
or operation.
INTRODUCTION
Bryant thermostats are wall-mounted, low-voltage thermostats
which maintain room temperature by controlling the operation of
a heating and air conditioning system. Separate heating and
cooling setpoints, plus auto changeover provide maximum comfort
and flexibility. Batteries are optional; temperature and mode
settings are preserved with the power off.
INSTALLATION CONSIDERATIONS
POWER
Note that all thermostats are dual powered where batteries can be
installed or in the presence of R and C (24vac) are not required. 2
AA batteries are furnished with the product.
MODELS
There are 3 different models. The 9th and 10th letters of the part
number indicate the model. These 2 letters also appear on the
package and on the circuit board. Be sure to have the proper
thermostat for the intended application. Models are:
AC 1-stage cool, 1-stage heat for AC systems only.
HP 1-stage cool, 2-stage heat for either HP, or AC with 2-stage
heat.
2S 2-stage cool, 2-stage heat for 2-speed AC systems, or
2-stage cool, 3-stage heat for 2-speed HP systems.
USE EACH ONLY FOR ITS INTENDED PURPOSE. SEE
TABLE 1.
INSTALLATION
I. THERMOSTAT LOCATION
Thermostat should be mounted:
Approximately 5 ft. (1.5m) from floor.
Close to or in a frequently used room, preferably on an inside
partitioning wall.
On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
Close to a window, on an outside wall, or next to a door leading
to the outside.
Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature-radiating object which may cause a false
reading.
Close to or in direct airflow from supply registers and return-air
grilles.
In areas with poor air circulation, such as behind a door or in
an alcove.
II. SELECT MODEL
AC Model (1-stage cool, 1-stage heat) is to be used for single-
stage heating and/or cooling applications only. It CANNOT be
used with optional outdoor temperature sensor. (See Table 1.)
HP Model (1-stage cool, 2-stage heat) can be used with a
single-speed heat pump (HP), or an air conditioner (AC) with a
2-stage furnace or fan coil. Software Option 5 selects HP/AC
operation. This thermostat comes configured from the factory as a
heat pump thermostat. Select AC in software Option 5 for AC
operation. When AC operation is selected, the O/W2 terminal is
converted from a reversing valve output (O) to a second-stage heat
output (W2). This output can be used to control 2-stage furnaces or
2-stage electric heat in fan coils. (See Table 1.)
2S Model is for 2-speed compressor systems only (HP and AC).
Output Y1 controls compressor low speed and output Y/Y2
controls compressor high speed. (See Table 1.)
HEIGHT (IN.) WIDTH (IN.) DEPTH (IN.)
3-1/2 5-3/4 1-3/8
Fig. 1—Bryant Non-Programmable Thermostat
TSTATBBNAC01-C
TSTATBBNHP01-C
TSTATBBN2S01-C
A04101
FAN
Installation, Start-Up
and Operating Instructions
NON-PROGRAMMABLE THERMOSTATS
Cancels: New II TSTAT-0-34
08-04
—1—
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - Installation, Start-Up

NOTE: Read the entire instruction manual before starting theinstallation.This symbol → indicates a change since the last issue.SAFETY CONSIDERATIONSRe

Page 2 - adjustment

WIRING DIAGRAM NOTES:1. Furnace must control its own second-stage heat operation via furnace control algorithm. Refer to indoor equipment Installation

Page 3

OPERATIONAL INFORMATIONFIVE-MINUTE COMPRESSOR TIMEGUARDThis timer prevents the compressor from starting unless it has been off for at least 5 minutes.

Page 4

A04105NON-PROGRAMMABLE THERMOSTAT CONFIGURATION RECORDDateOwner/OperatorA) Hardware Configuration Seal hole in wall.Thermostat Model No.B) Mode

Page 5

III. INSTALL THERMOSTATWARNING: ELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.Before installing thermo

Page 6

rate. However, a limiting feature will not allow more than 6equipment cycles per hour, regardless of setting. Values can rangefrom 1 to 9. Factory def

Page 7

TO SELECT:1. Enter configuration mode (if not already there).2. Use up and down buttons to display Option 07. The SETicon should be off.3. Press MODE

Page 8

6. Use up and down buttons to select another Option, or pressFAN button to exit configuration mode.M. Option 19 — Equipment PresentThis selection info

Page 9

TABLE 2—NON-PROGRAMMABLE -C THERMOSTAT QUICK REFERENCETHERMOSTAT OUTPUTTSTAT Model Outdoor Unit Option 524vHotCommon FanHeatStage 1HeatStage 2HeatStag

Page 10

Fig. 8—Two-Speed Air Conditionerwith Single-Stage FurnaceA0400924 VAC HOT24 VAC COMMHEAT STAGE 1COOL STAGE 2FANRCGW/W1Y/Y2RCN/ACOOL STAGE 1N/AOUTDOORS

Page 11

Fig. 12—Single-Speed Air Conditionerwith Variable Speed (FK4D, FV, 40FK) Fan CoilRY/Y2RYW/W1W1CMODEL AC 01-CTHERMOSTATEASY SELECTTERMINAL BOARDSINGLE-

Page 12 - factory default = 0)

Fig. 14—Two-Speed Air Conditioner with Variable-Speed(FK4D, FV4, 40FK) Fan CoilA0401224 VOLT HOT24 VOLT COMMFANCOOL STAGE 2HEAT STAGE 1RY/Y2RY2CCCRY1M

Commentaires sur ces manuels

Pas de commentaire