Installation Instructions286B (2 -- 5 TONS)289B (3 TON TROPHY)EVOLUTIONt SERIES 2--STAGE HEAT PUMPWITH PURONRREFRIGERANTSAFETY CONSIDERATIONSImproper
10Field ConnectionsOn non--communicating (non--Evolution) system, the two--stagecontrol receives 24vac low--voltage control system inputs throughthe R
11Contactor Shorted DetectionIf there is compressor voltage sensed when there is no demand forcompressor operation, the contactor may be stuck closed
12OAT Thermistor must belocked in place with spheri-cal nib end facing towardsthe front of the control boxFig. 8 -- Outdoor Air Thermistor (OAT) Attac
13RVS/Heat Stage 2 O/B W2Heat Stage 1 W/W1Compressor Low Y1Compressor High Y/Y2Fan G24VAC Hot Heating Rh24VAC Hot Cooling RcDry Contact 1 D1Dry Contac
14FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing and sheetmetal edges to
2INSULATIONSUCTION TUBELIQUID TUBEOUTDOOR WALL INDOOR WALLLIQUID TUBESUCTION TUBEINSULATIONCAULKHANGER STRAP(AROUND SUCTIONTUBE ONLY)JOIST1” (25.4 mm)
3Make Piping Connections!WARNINGPERSONAL INJURY AND UNIT DAMAGEHAZARDFailure to follow this warning could result in personalinjury or death.Relieve pr
4Install Liquid--Line Filter Drier Indoor!WARNINGUNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could result in personal injuryor equi
5Make Electrical Connections!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personalinjury or death.Do not supply power
6Airflow Selection for Variable Speed Furnaces(non--communicating)The variable speed furnaces provide blower operation to match thecapacities of the c
7Communication and Status Function LightsFor Evolution Control only, Green communications (COMM)LightA green LED (COMM light) on the outdoor board (se
8UTILITY RELAY *UTILITY SIGNALOPEN RELAY* SUPPLIED BY UTILITY PROVIDERMODEL PLUGA06525LLSLiquid Line SolenoidMODEL PLUGA06526Fig. 6 -- 2--Stage Contr
9Status code 4 shows the fan delay defeat is active (no delay).Status code 3 shows that it is not active (20 second delay).The code will continue to b