Page 1 - Product Data

580JGAS HEAT/ELECTRIC COOLING PACKAGED ROOFTOP3 TO 12.5 NOMINAL TONSProduct DataC08515(Unit shown with optional louvered hail guard.)the environmental

Page 2 - Certified to ISO 9001:2008

10Table 5 – HEATING RATING TABLE -- LOW NOx1UNITGAS HEATLOW NOx HEAT EXCHANGERTEMP RISE(DEG F)THERMALEFFICIENCY(%)AFUE(%)INPUT / OUTPUTSTAGE 1 (MBH)IN

Page 3 - FEATURES AND BENEFITS

11Table 7 – MINIMUM -- MAXIMUM AIRFLOW RATINGS -- NATURAL GAS & PROPANEUNIT HEAT LEVELCOOLING HEATINGMINIMUM MAXIMUM MINIMUM MAXIMUM580J*04LOW900

Page 4 - MODEL NUMBER NOMENCLATURE

12Table 8 – PHYSICAL DATA (COOLING) 3 -- 6 TONS580J*04A 580J*05A 580J*06A 580J*07ARefrigeration System#Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/

Page 5

13Table 9 – PHYSICAL DATA (HEATING) 3 -- 6 TONS580J*04 580J*05 580J*06 580J*07Gas Connection#ofGasValves 1 1 1 1Nat. gas supply line press (in. w.g.)/

Page 6

14Table 10 – PHYSICAL DATA (COOLING) 7.5 -- 8.5 TONS580J*08A 580J* 08D 580J*09A 580J*09DRefrigeration System#Circuits/#Comp./Type 1/1/Scroll 2/2/Scrol

Page 7

15Table 11 – PHYSICAL DATA (COOLING) 10 -- 12.5 TONS580J*12A 580J*12D 580J*14DRefrigeration System#Circuits/#Comp./Type 1/1/Scroll 2/2/Scroll 2/2/Scro

Page 8

16Table 12 – PHYSICAL DATA (HEATING) 7.5 -- 12.5 TONS580J*08 580J*09 580J*12 580J*14Gas Connection#ofGasValves 1 1 1 1Nat. gas supply line press (in.

Page 9

17CURBS & WEIGHTS DIMENSIONS -- 580J*04--07C08523Fig. 1 -- Dimensions 580J 04--07580J

Page 10

18CURBS & WEIGHTS DIMENSIONS -- 580J*04--07 (cont.)C08599Fig. 2 -- Dimensions 580J 04--07CBADC08337Fig. 3 -- Service ClearanceLOC DIMENSION CONDIT

Page 11

19CURBS & WEIGHTS DIMENSIONS -- 580J*04--07 (cont.)CONNECTORPKG. ACCY.BCD ALTDRAINHOLEGAS POWER CONTROLACCESSORYPOWERCRBTMPWR001A011’-911/16”[551]

Page 12

2TABLE OF CONTENTSPAGEFEATURES AND BENEFITS 3...MODEL NUMBER NOMENCLATURE 4...FACTORY OPTIONS AND/OR ACCESSORIES 6...AHRI

Page 13

20CURBS & WEIGHTS DIMENSIONS -- 580J*08--12C10496Fig. 5 -- Dimensions 580J 08--12580J

Page 14

21CURBS & WEIGHTS DIMENSIONS -- 580J*08--12 (cont.)C08526Fig. 6 -- 580J 08--12CBADC08337Fig. 7 -- Service ClearanceLOC DIMENSION CONDITIONA48---in

Page 15

22CURBS & WEIGHTS DIMENSIONS -- 580J*08--14580J580J*08 –08 – 1414UNIT SIZEROOFCURBACCESSORYCRRFCURB003A01CRRFCURB004A011’ - 2”(356)2’ - 0”(610)TYP

Page 16

23CURBS & WEIGHTS DIMENSIONS -- 580J 14C10508Fig. 9 -- Dimensions 580J--14580J

Page 17

24CURBS & WEIGHTS DIMENSIONS -- 580J 14 (cont.)C08528Fig. 10 -- Dimensions 580J--14CBADC08337Fig. 11 -- Service ClearanceLOC DIMENSION CONDITIONA4

Page 18 - Fig. 3 -- Service Clearance

25OPTIONS & ACCESSORY WEIGHTSOPTION / ACCESSORYOPTION / ACCESSORY WEIGHTS04 05 06 07 08 09 12 14lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kgP e

Page 19 - Fig. 4 -- Roof Curb Details

26APPLICATION DATAMin operating ambient temp (cooling):In mechanical cooling mode, your Bryant rooftop unit cansafely operate down to an outdoor ambie

Page 20

27APPLICATION DATA (cont.)Sizing a rooftopBigger isn’t necessarily better. While an air conditionerneeds to have enough capacity to meet the design lo

Page 21 - Fig. 7 -- Service Clearance

28SELECTION PROCEDURE (WITH 580J*07A EXAMPLE)1I. Determine cooling and heating loads.Given:Mixed air dry bulb 80_F(27_C)Mixed air wet bulb 67_F(19_C)A

Page 22 - Fig. 8 -- Roof Curb Details

29Table 13 – COOLING CAPACITIES 1--STAGE COOLING 3 TONS580J*04A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75 80

Page 23 - Fig. 9 -- Dimensions 580J--14

3FEATURES AND BENEFITSS Single cooling stage models are available from 3 -- 10 ton.S Two cooling stage models are available from 7.5 -- 12.5 ton.S SEE

Page 24 - Fig. 11 -- Service Clearance

30Table 14 – COOLING CAPACITIES 1--STAGE COOLING 3 TONS580J04 (3 TONS) --- UNIT WITH PERFECT H UMIDITY SYSTEM IN SUBCOOLING MODEA i r E n t e r i n g

Page 25 - Where Available

31Table 15 – COOLING CAPACITIES 1--STAGE COOLING 4 TONS580J*05A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75 80

Page 26 - APPLICATION DATA

32Table 16 – COOLING CAPACITIES 1--STAGE COOLING 4 TONS580J05 (4 TONS) --- UNIT WITH PERFECT H UMIDITY SYSTEM IN SUBCOOLING MODEA i r E n t e r i n g

Page 27 - APPLICATION DATA (cont.)

33Table 17 – COOLING CAPACITIES 1--STAGE COOLING 5 TONS580J*06A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75 80

Page 28

34Table 18 – COOLING CAPACITIES 1--STAGE COOLING 5 TONS580J06 (5 TONS) --- UNIT WITH PERFECT H UMIDITY SYSTEM IN SUBCOOLING MODEA i r E n t e r i n g

Page 29

35Table 19 – COOLING CAPACITIES 1--STAGE COOLING 6 TONS580J*07A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75 80

Page 30

36Table 20 – COOLING CAPACITIES 1--STAGE COOLING 6 TONS580J07 (6 TONS) --- UNIT WITH PERFECT H UMIDITY SYSTEM IN SUBCOOLING MODEA i r E n t e r i n g

Page 31

37Table 21 – COOLING CAPACITIES 1--STAGE COOLING 7.5 TONS580J*08A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EA (db)75 80 85 75 8

Page 32

38Table 22 – COOLING CAPACITIES 2--STAGE COOLING 7.5 TONS580J*08D(RTPF & Novation)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EA (d

Page 33

39Table 23 – COOLING CAPACITIES 2--STAGE COOLING (RTPF ONLY) 7.5 TONS580J08 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODETE

Page 34

4MODEL NUMBER NOMENCLATURE12345678910111213141516175 8 0 J E 0 6 A 0 7 2 A 1 A 0 A A____________ ______ ________ ______Unit Type Packaging580J = Cooli

Page 35

40Table 24 – COOLING CAPACITIES 1--STAGE COOLING 8.5 TONS580J*09A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75

Page 36

41Table 25 – COOLING CAPACITIES 2--STAGE COOLING 8.5 TONS580J*09D(RTPF)AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 8

Page 37

42Table 26 – COOLING CAPACITIES 2--STAGE COOLING (RTPF ONLY) 8.5 TONS580J09 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODETE

Page 38

43Table 27 – COOLING CAPACITIES 1--STAGE COOLING 10 TONS580J*12A(RTPF)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (db)75 80 85 75 8

Page 39

44Table 28 – COOLING CAPACITIES 2--STAGE COOLING 10 TONS580J*12D(RTPF & Novation)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT (d

Page 40

45Table 29 – COOLING CAPACITIES 2--STAGE COOLING (RTPF ONLY) 10 TONS580J12 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODETEM

Page 41

46Table 30 – COOLING CAPACITIES 2--STAGE COOLING 12.5 TONS580J*14D(RTPF & Novation)AMBIENT TEMPERATURE85 95 105 115EAT (db) EAT (db) EAT (db) EAT

Page 42

47Table 31 – COOLING CAPACITIES 2--STAGE COOLING (RTPF ONLY) 12.5 TONS580J14 COOLING CAPACITIES, UNIT WITH PERFECT HUMIDITY SYSTEM IN SUBCOOLING MODET

Page 43

48Table 32 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)Economizer3 --- 6 T O N SCFM (in. wg)600 800 1000 1250 1500 1750 2000 2250 250

Page 44

49FAN PERFORMANCETable 33 – 580J*04 1 PHASE 3 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 45

5Table 1 – FACTORY--INSTALLED OPTIONS AND FIELD--INSTALLED ACCESSORIESCATEGORY ITEMFACTORYINSTALLEDOPTIONFIELDINSTALLEDACCESSORYCabinet Thru---the---b

Page 46

50FAN PERFORMANCE (cont.)Table 35 – 580J*04 3 PHASE 3 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 47

51FAN PERFORMANCE (cont.)Table 37 – 580J*05 1 PHASE 4 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 48 - Perfect Humidity

52FAN PERFORMANCE (cont.)Table 39 – 580J*05 3 PHASE 4 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 49 - FAN PERFORMANCE

53FAN PERFORMANCE (cont.)Table 41 – 580J*06 1 PHASE 5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 50 - FAN PERFORMANCE (cont.)

54FAN PERFORMANCE (cont.)Table 43 – 580J*06 3 PHASE 5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 51

55FAN PERFORMANCE (cont.)Table 45 – 580J*07 3 PHASE 6 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP

Page 52

56FAN PERFORMANCE (cont.)Table 47 – 580J*08 3 PHASE 7.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM B

Page 53

57FAN PERFORMANCE (cont.)Table 49 – 580J*09 3 PHASE 8.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM B

Page 54

58FAN PERFORMANCE (cont.)Table 51 – 580J*12 3 PHASE 10 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BH

Page 55

59FAN PERFORMANCE (cont.)Table 53 – 580J*14 3 PHASE 12.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM

Page 56

6FACTORY OPTIONS AND/OR ACCESSORIESEconomizer (dry--bulb or enthalpy)Economizers save money. They bring in fresh, outside airfor ventilation; and prov

Page 57

60FAN PERFORMANCE (cont.)Table 55 – PULLEY ADJUSTMENTUNITMOTOR/DRIVECOMBOMOTOR PULLEY TURNS OPEN0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0041phaseSta

Page 58

61ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCE050010001500200025000 0.05 0.1 0.15 0.2 0.25 0.3RETURN DUCT STATIC PRES SURE (in. wg)RELIEF FLOW (CF

Page 59

62ELECTRICAL INFORMATIONTable 56 – 580J*04A 1--Stage Cooling 3 TONSV --- P h --- H zVOLTAGERANGECOMP (ea) OFM (ea) IFMRLA LRA WATTS FLA TYPEMaxWATTSMa

Page 60

63ELECTRICAL INFORMATION (cont.)Table 59 – 580J*07A 1--Stage Cooling 6 TONSV --- P h --- H zVOLTAGERANGECOMP (ea) OFM (ea) IFMRLA LRA WATTS FLA TYPEMa

Page 61 - Horizontal Power Exhaust

64ELECTRICAL INFORMATION (cont.)Table 62 – 580J*09A 1--Stage Cooling 8.5 TONSV --- P h --- H zVOLTAGERANGECOMP (ea) OFM (ea) IFMRLA LRA WATTS FLA TYPE

Page 62 - ELECTRICAL INFORMATION

65ELECTRICAL INFORMATION (cont.)Table 65 – 580J*12D 2--Stage Cooling 10 TONSV --- P h --- H zVOLTAGERANGECOMP (Cir 1) COMP (Cir 2) OFM (ea) IFMRLA LRA

Page 63

66Table 67 – MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.UNITNOM.V --- P h --- H zIFMTYPECOMBUSTIONFAN MOTORFLAPOWEREXHAUSTFLANO C.O. or UNPWRD C.O.N

Page 64

67TABLE 67 (cont.) MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.UNITNOM.V --- P h --- H zIFMTYPECOMBUSTIONFAN MOTORFLAPOWEREXHAUSTFLANO C.O. or UNPWRD

Page 65

68TABLE 67 (cont.) MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.LEGEND:C.O. --- Convenience outletDISC --- DisconnectFLA --- Full load ampsIFM --- Ind

Page 66 - See notes on page 68

69Table 68 – MCA/MOCP DETERMINATION W/ PWRD C.O.UNITNOM.V --- P h --- H zIFMTYPECOMBUSTIONFAN MOTORFLAPOWEREXHAUSTFLAw/ PWRD C.O.NO P.E. w/ P.E. (pwrd

Page 67 - See notes on next page

7FACTORY OPTIONS AND/OR ACCESSORIES (cont.)The Legacy Line 580J*04--14 rooftop coupled with thePerfect Humidity system is capable of operating in norm

Page 68

70TABLE 68 (cont.) MCA/MOCP DETERMINATION W/ PWRD C.O.UNITNOM.V --- P h --- H zIFMTYPECOMBUSTIONFAN MOTORFLAPOWEREXHAUSTFLAw/ PWRD C.O.NO P.E. w/ P.E.

Page 69

71TYPICAL WIRING DIAGRAMSC08518Fig. 18 -- 1--Stage Cooling Typical Power Diagram580J

Page 70

72TYPICAL WIRING DIAGRAMS (cont.)C08577Fig. 19 -- 2--Stage Cooling Typical Power Diagram580J

Page 71 - TYPICAL WIRING DIAGRAMS

73C08524Fig. 20 -- 1--Stage Typical Wiring Diagram580J

Page 72

74C08578Fig. 21 -- 2--Stage Typical Wiring Diagram580J

Page 73

75SEQUENCE OF OPERATIONGeneralThe sequence below describes the sequence of operationfor an electromechanical unit with and without a factoryinstalled

Page 74

76SEQUENCE OF OPERATION (cont.)On the initial power to the EconoMi$er IV control, it willtake the damper up to 2 1/2 minutes before it begins topositi

Page 75 - SEQUENCE OF OPERATION

77SEQUENCE OF OPERATION (cont.)COMPCOND COILPERFECT HUMIDITY COILEVAP COILINDOOR ENTERINGAIROUTDOOR AIRMETERINGDEVICECLOSED VALVEOPEN VALV

Page 76 - SEQUENCE OF OPERATION (cont.)

78GUIDE SPECIFICATIONS -- 580J*04--14Note about this specification:Bryant wrote this specification in the 2004 version of the “Masterformat” as publis

Page 77

7911. Shall have a battery back--up capable of a minimum of 10,000 hours of data and time clock retention during poweroutages.12. Shall have built--in

Page 78 - HVAC Guide Specifications

8Table 2 – AHRI COOLING RATING TABLE 1--STAGE COOLINGUNITCOOLINGSTAGESNOM.CAPACITY(TONS)NETCOOLINGCAPACITY(MBH)TOTALPOWER (kW)SEER EER IEER04A 1 3 34.

Page 79

802. Factory assembled, single--piece heating and cooling rooftop unit. Contained within the unit enclosure shall be allfactory wiring, piping, contro

Page 80

815. Base Raila. Unit shall have base rails on a minimum of 2 sides.b. Holes shall be provided in the base rails for rigging shackles to facilitate ma

Page 81

82c. Burners shall incorporate orifices for rated heat output up to 2000 ft (610m) elevation. Additional accessorykits may be required for application

Page 82

835. Standard All Aluminum Novation Coils:a. Standard condenser coils shall have all aluminum NOVATION Heat Exchanger Technology design consistingof a

Page 83

84b. Shall use sealed, permanently lubricated ball--bearing type.c. Blower fan shall be double--inlet type with forward--curved blades.d. Shall be con

Page 84

854. Perfect Humidity Dehumidification System:a. The Perfect Humidity Dehumidification System shall be factory installed in single stage 580J04--07 an

Page 85

86b. Minimum of four connection locations per unit.13. Propeller Power Exhaust:a. Power exhaust shall be used in conjunction with an integrated econom

Page 86 - Catalog No. PDS580J---08

9Table 4 – HEATING RATING TABLE -- NATURAL GAS & PROPANEUnits Gas HeatAL/SS HEAT EXCHANGERTEMP RISE(DEG F)THERMALEFFICIENCY(%)AFUE(%)INPUT / OUTPU