installation, start-up and
service instructions
IN-CEILING CASSETTE
FAN COIL UNITS
619FNF
619FNQ
Sizes 018-03036
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
I. Step 1 — Complete Pre-Installation Checks . . . . . . 2
II. Step 2 — Locating and Mounting the Unit. . . . . . . . 6
III. Step 3 — Locating and Mounting the Room
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
IV. Step 4 — Complete Refrigerant Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
V. Step 5 — Make Electrical Connections . . . . . . . . . 11
INSTALLATION OPTIONS . . . . . . . . . . . . . . . . . . . . . . . .19-22
I. Fresh Air Intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
II. Conditioned Air Supply to Adjacent Room . . . . . . 19
III. Room Controller Configuration Setup . . . . . . . . . . 21
IV. Louver Mode Selection . . . . . . . . . . . . . . . . . . . . . . 21
V. Main Board Configuration. . . . . . . . . . . . . . . . . . . . 21
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22,23
SERVICE AND MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . 23
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .23,24
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as
cleaning and replacing filters. All other operations should be
performed by trained service personnel. When working on air
conditioning equipment, observe safety precautions in litera-
ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for brazing operations. Have fire extin-
guisher available. Read these instructions thoroughly. Con-
sult local building codes and the National Electrical Code
(NEC) for special installation requirements.
GENERAL
These instructions cover the installation, start-up and service
of in-ceiling cassette fan coil units. See Fig. 1.
The following accessories can be used with 619FNF, FNQ
units. See the price pages for part numbers and additional
information for the following accessories:
photocatalytic and electrostatic filter with mount
air supply outlet obstruction kit
wired room controller
room controller wiring kit for multiple units
zone manager kit for multiple units
zone manager
infrared remote kit
WARNING: Before installing or servicing system,
always turn off main power to system. There may be
more than one disconnect switch. Turn off accessory
heater power if applicable. Electrical shock can cause
serious personal injury.
CAUTION: This system uses Puron® refrigerant
(R-410A), which has higher pressures than R-22 and
other refrigerants. No other refrigerant may be used in
this system. All equipment must be designed to handle
R-410A refrigerant. If unsure about equipment, consult
the equipment manufacturer.
CAUTION: Do not operate the unit without a filter
or with the grille removed. Damage to the unit or per-
sonal injury may result.
Fig. 1 — 619FNF, FNQ Unit
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - FAN COIL UNITS

Cancels: New II 619F-18-14/1/06installation, start-up andservice instructionsIN-CEILING CASSETTEFAN COIL UNITS619FNF619FNQSizes 018-03036CONTENTSPageS

Page 2

—10—IV. STEP 4 — COMPLETE REFRIGERANT PIPINGCONNECTIONSIMPORTANT: During unit installation make the refrigerantconnections first and then the electric

Page 3 - 619FNF018

—11—V. STEP 5 — MAKE ELECTRICAL CONNECTIONS See Tables 6A and 6B for electrical information.A. Units With Electric HeaterThe unit is equipped with tw

Page 4

—12—Room ControllerConnectionsGroundConnectionOutdoor UnitConnectionsLowVoltageHighVoltagePowerConnectionsFig. 21 — 619FNF Unit Matched to 538ENF Outd

Page 5

—13—LowVoltageHighVoltageRoom ControllerConnectionsOutdoor UnitConnectionsPowerConnectionsGroundConnectionFig. 22 — 619FNQ Unit Matched to 538ENF Outd

Page 6 - Max. 2 louvers closed

—14—LowVoltageHighVoltageRoom ControllerConnectionsGroundConnectionOutdoor UnitConnectionsPowerConnectionsFig. 23 — 619FNQ Unit Matched to 538QNF Outd

Page 7

—15—ETTESSAC LABOLG 619FNFRESNEDNOC ROODTUO 538ENFNOTE 6NOTE 5NOTE 4YALPSIDRIA-MTLIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU OT

Page 8 - 7-7/8”(200 mm)

—16—ETTESSAC LABOLG QNF619RESNEDNOC ROODTUO FNE538NOTE 6NOTE 5YALPSIDRIA-MT LIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU O

Page 9 - 0mm)7("4/3-2

—17—ETTESSAC LABOLG 619FNQRESNEDNOC ROODTUO 538QNFNOTE 6NOTE 5YALPSIDRIA-MT LIOC-MT"D" RALUDOMBCP1 LORTNOCREPPOC ERABTCENNOCSID TINU O

Page 10 - Indoor end

—18—INTERNAL CONTROL PANEL619FNF018CapacitorGMC boardElectric heater board(only on models with electric heater)TransformerHoles for fixing panel in po

Page 11

—19—C. Wiring the Room ControllerThe room controller is capable of controlling from 1 to 6 fancoil units. The total run length of the wire connecting

Page 12 - (Cooling Only System)

—2—INSTALLATIONI. STEP 1 — COMPLETE PRE-INSTALLATION CHECKSA. Unpack Unit (See Fig. 1)Move the unit to final location. The grille panel and theremote

Page 13

—20—4.72”(120)ØA BØA Ø CDuct connection flangeClip1/4" (6 mm) neoprene gasketInsulated flexible ductFresh air intakeConditioned air supply to an

Page 14 - (Heat Pump System)

—21—III. ROOM CONTROLLER CONFIGURATION SETUPTo configure the room controller, press the Mode button for5 seconds. After 5 seconds, “10” will appear. T

Page 15 - BCP1 LOR

—22—Table 8 — Modular Platform D Unit Configuration ValuesOnly the current value being displayed is transmitted. Oncethe Fan button is pressed, the ro

Page 16

—23—4. Ensure that the filters and return air grilles havebeen installed and that the discharge louvers arecorrectly positioned.SERVICE AND MAINTENANC

Page 17 - "D" R

Copyright 2006 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 02-619F0001-IIGreenLEDRed LEDYellow LEDRemote controlsignal receiver

Page 18

—3—2'-4-11/32"(720)1'-9-21/32"(550))515("23/98-'11-7/8"(47)1'-11-7/16"(595))318("8-'2)069("

Page 19 - Diagram 1

—4—Table 4A — 619FNF Physical Data LEGEND*See Table 3 for factory charge and additional field charge requirements.SYSTEM SIZE 018

Page 20 - Air intake grille

—5—Table 4B — 619FNQ Physical Data LEGEND*See Table 3 for factory charge and additional field charge requirements.SYSTEM SIZ

Page 21

—6—II. STEP 2 — LOCATING AND MOUNTING THE UNITA. Locating the UnitInstall the unit as centrally as possible in the room. The air-flow direction can be

Page 22

—7—The condensate may be discharged at a maximum height of77/8 in. above the unit, as long as the ascending tube is verti-cal and aligned with the dra

Page 23 - Table 9 — Fault Codes

—8—III. STEP 3 — LOCATING AND MOUNTING THE ROOMCONTROLLERA. Locating the Room ControllerSee Fig. 14 for room controller dimensions. If the air sensori

Page 24

—9—B. Mounting the Room Controller (Fig. 15-17)Unscrew the side fixing screw. Open the room controller rearmounting base to expose the mounting holes.

Commentaires sur ces manuels

Pas de commentaire