NOTE: Read the entire instruction manual before starting theinstallation.TABLE OF CONTENTSSAFETY CONSIDERATIONS ...
Fig. 12—Wiring Schematics (208/230-3-60)C00134—10—
Fig. 13—Wiring Schematics (460-3-60)C00135—11—
TABLE 5—ELECTRICAL DATA—601AUNIT 601ASIZEV-PH-HZVOLTAGERANGECOMPRESSOROFMFLAIFMFLAELECTRIC HEAT SINGLE POINT POWER SUPPLYMIN MAX RLA LRANominalkW*FLA
TABLE 6—ELECTRICAL DATA—602AUNIT 602ASIZEV-PH-HZVOLTAGERANGECOMPRESSOROFMFLAIFMFLAELECTRIC HEAT SINGLE POINT POWER SUPPLYMIN MAX RLA LRA Nominal kW* F
leads are inside the unit, run leads up the high-voltage raceway tothe line wiring splice box (See Fig. 12–17). On all 3-phase units,connect the leads
PRE-START-UPWARNING: Failure to observe the following warningscould result in serious personal injury or death:1. Follow recognized safety practices a
IMPORTANT: Three-phase, scroll compressors are directionoriented. Unit must be checked to ensure proper compressor3-phase power lead orientation. If n
E. LOW CHARGE COOLINGUse Cooling Charging Charts (Fig. 24-33). Vary refrigerant untilthe conditions of the chart are met. Note that charging charts ar
MAINTENANCETo ensure continuing high performance, and to minimize thepossibility of premature equipment failure, periodic maintenancemust be performed
For longer life, operating economy, and continuing efficiency,clean accumulated dirt and grease from the blower wheel andmotor annually.WARNING: Disco
WARNING: Improper installation, adjustment, alter-ation, service, maintenance, or use can cause explosion,fire, electric shock, or other occurrences,
5. Ensure that setscrew engages the flat area on the motor shaftwhen tightening.6. Replace grille.V. ELECTRICAL CONTROLS AND WIRINGInspect and check t
Fig. 24—Cooling Charging Chart, 601A030 UnitsC00028SUCTION LINE PRESSURE (KILOPASCALS)SUCTION LINE PRESSURE (PSIG)-7 -1 4 10 16 21 27SUCTION LINE TEMP
IX. LIQUID LINE STRAINERSThe liquid line strainers (to protect metering devices) are made ofwire mesh and are located in the liquid lines on the inlet
689 100.030.040.050.060.070.080.090.0207276345414483551620SUCTION LINE PRESSURE (KILOPASCALS)SUCTION LINE PRESSURE (PSIG)20.0-7 272116104-180.070.060.
TABLE 9—FILTER PRESSURE DROP (IN. WG)FILTER SIZECFM500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 230020X20X10.0
TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHARTSYMPTOM CAUSE REMEDYCompressor and outdoorfan will not startPower Failure Call power companyFuse blo
TABLE 11—COOLING AND HEATING TROUBLESHOOTING CHART (CONT’D)SYMPTOM CAUSE REMEDYSuction pressure too low(Cool) Dirty air filter Replace filter(Heat) Ou
Fig. 2—601A030-042/602A030-036 Unit DimensionsUNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTUNIT HEIGHTIN. (MM)”A”CENTER OF GRAVITYIN. (MM)Lb Kg X Y Z601A
Fig. 3—601A048-060/602A042-060 Unit DimensionsUNIT ELECTRICAL CHARACTERISTICSUNIT WEIGHTUNIT HEIGHTIN. (MM)”A”CENTER OF GRAVITYIN. (MM)Lb Kg X Y Z601A
3. Place each of the 4 metal lifting brackets into the riggingholds in the composite pan.4. Thread lifting bracket strapping around bottom perimeter o
Fig. 5—Roof Curb DimensionsUNIT SIZE ODS CATALOG NUMBERAIN. (MM)BIN. (MM)CIN. (MM)DIN. (MM)601A030-042 602A030-036CPRFCURB006A00 8 (203) 11(279) 161/2
3. Size ductwork for cooling air quantity (cfm). The minimumair quantity for proper electric heater operation is listed inTables 3 and 4. Heater limit
TABLE 1—PHYSICAL DATAUNIT SIZE 601A030 601A036 601A042 601A048 601A060NOMINAL CAPACITY (ton) 2-1/2 3 3-1/2 4 5OPERATING WEIGHT (lb.) 287 291 323 353 4
VII. INSTALL ELECTRICAL CONNECTIONSWARNING: The unit cabinet must have an uninter-rupted, unbroken electrical ground to minimize the pos-sibility of p