DESCRIPTION
The 579/580 gas heating/electric cooling rooftop units are de-
signed to deliver optimum performance and reliability in a com-
mercial rooftop unit.
The 3 to 25 ton units are one-piece gas heating, electric cooling
units that are prewired and precharged with R-22 at the factory,
making jobsite installation easy. Every unit is factory run-tested
prior to shipment to ensure reliable installation.
The 579/580 units are designed to be field-convertible from ver-
tical supply/return to horizontal supply/return (180-300 units
require an accessory horizontal roof curb or horizontal adapter),
making them easily adaptable to a wide variety of new construc-
tion and replacement applications. For vertical supply/return
jobs, ductwork can be connected directly to the roof curb, allow-
ing ductwork to be completed before unit is available for instal-
lation. All units include easily replaceable internal filters.
The 579/580 units are available in a range of heating sizes and
voltage options to meet most job requirements. Low-voltage ter-
minal blocks make wiring connections quick and simple.
All units are listed with either UL (Underwriters’ Laboratories) or
ETL Laboratories and with CSA (Canadian Standards Associa-
tion), UL Canada, or Warnock Hersey. All units are ARI (Air-
Conditioning & Refrigeration Institute) approved (except the 300
unit, which is beyond the scope of the ARI certification program)
and comply with ASHRAE Standard 62 (American Society of
Heating, Refrigeration, and Air Conditioning Engineers).
STANDARD FEATURES
EFFICIENT DESIGN means cooling and heating energy sav-
ings. Standard units have EERs (energy efficiency ratios) of up
to 9.2 and SEERs (seasonal energy efficiency ratios) of 10.0
(036-060 belt drive units only). The 580D units have an AFUE
(Annual Fuel Utilization Efficiency) rating of 80.0% with a Cali-
fornia Seasonal Efficiency rate of 75.8% or better. All 579/580
units have a steady-state efficiency of 80.0%.
THE FACTORY-ASSEMBLED PACKAGE is a compact, fully
self-contained electric cooling/gas heating unit that is prewired,
prepiped, and precharged for minimum installation expense.
UNITS MAY BE CONVERTED TO HORIZONTAL DIS-
CHARGE in the field. The units can be modified at the jobsite to
fit a variety of applications (180-300 units require an accessory
horizontal supply/return roof curb or a horizontal supply/return
adapter).
INTERNAL RETURN-AIR FILTERS are provided. Two-in.
throwaway filters are provided standard on all units, and can be
easily accessed through the tool-less filter access panels. There
is no need to field-fabricate filter racks or install external filter
accessories.
COMPRESSOR PROTECTION is assured. The 036-150 units
have an internal pressure relief valve and line break (current
overload) protections, and the 180-300 units have high- and
low-pressure protection external to the compressor. These pro-
tections prohibit operation under abnormal unit conditions.
Model 580D036-072
Model 580D090-150
Model 579F180,216
Model 579F240,300
Bryant
Air Conditioning
COMMERCIAL
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Model 579F/580D
Sizes 036-300
3to25Tons
Form No. PDS 580D.36.4B
Vue de la page 0
1 2 3 4 5 6 ... 63 64

Résumé du contenu

Page 1 - Model 579F/580D

DESCRIPTIONThe 579/580 gas heating/electric cooling rooftop units are de-signed to deliver optimum performance and reliability in a com-mercial roofto

Page 2 - CONTENTS

DIMENSIONAL DRAWING — 579F240,300UNIT579FCORNER WEIGHT* DIMENSIONSABCD A B C D ELb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in.

Page 3

DIMENSIONAL DRAWING — ROOF CURB, 580D036-072UNIT SIZE580D‘‘B’’ ‘‘C’’‘‘D’’ ALTDRAINHOLE‘‘E’’GAS‘‘F’’POWER‘‘G’’CONTROLCONNECTORPACKAGEACCESSORY036-0721-

Page 4

DIMENSIONAL DRAWING — ROOF CURB, 580D090-150ROOF CURBACCESSORY‘‘A’’UNIT SIZE580DCRRFCURB003A0018-29[356]090-150CRRFCURB004A0028-09[610]UNIT SIZE580D‘‘

Page 5 - MODEL DESCRIPTION

DIMENSIONAL DRAWING — HORIZONTAL AND VERTICAL ROOF CURBS ANDHORIZONTAL ADAPTER, 579F180-300NOTE: To prevent the hazard of stagnant water build-up in t

Page 6 - CAPACITY RATINGS

DIMENSIONAL DRAWING — HORIZONTAL ADAPTER INSTALLATION — 579F216-300NOTE: 389210-201 and 389211-201 are fully factory preassembledhorizontal adapters w

Page 7

SPECIFICATIONS — 580D036-072UNIT SIZE 036 048 060 072NOMINAL CAPACITY (tons) 3456OPERATING WEIGHT (lb)UnitAl/Al* 460 470 490 565EconomizerVarislide™ 3

Page 8

SPECIFICATIONS — 580D036-072 (cont)UNIT SIZE 036 048 060 072FURNACE SECTION MediumHeatHighHeatLowHeatMediumHeatHighHeatLowHeatMediumHeatHighHeatLowHea

Page 9

SPECIFICATIONS — 580D090-150UNIT SIZE 090 102 120 150NOMINAL CAPACITY (tons) 71⁄281⁄210 121⁄2OPERATING WEIGHT (lb)UnitAl/Al* 870 880 1035 1050Economiz

Page 10

SPECIFICATIONS — 580D090-150 (cont)UNIT SIZE 090 102 120 150FURNACE SECTION LowHeatMediumHeatHighHeatLowHeatMediumHeatHighHeatLowHeatMediumHeatHighHea

Page 11

SPECIFICATIONS — 579F180-300UNIT SIZE180216 240 300208/230, 460 v 575 vNOMINAL CAPACITY (tons) 15 18 20 25OPERATING WEIGHT (lb)UnitAl/Al* 1604/1624\ 1

Page 12

DUAL COMPRESSORS AND DUAL REFRIGERATION CIR-CUITS (090-150 and 216-300 units) are provided. Two com-pressors, each on its own independent circuit, pro

Page 13

SPECIFICATIONS — 579F180-300 (cont)UNIT SIZE 180 216 240 300FURNACE SECTION Low Heat High Heat Low Heat Low Heat High Heat Low Heat High HeatRollout S

Page 14

SELECTION PROCEDURE (with 579F180270 example)I DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS:Given:Total Cooling Capacity Required

Page 15 - SPECIFICATIONS — 580D036-072

GROSS COOLING CAPACITIES580D036 (3 TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacity MBtuhCom

Page 16

GROSS COOLING CAPACITIES (cont)580D060 (5 TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacity M

Page 17 - SPECIFICATIONS — 580D090-150

GROSS COOLING CAPACITIES (cont)580D090 (71⁄2TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacity

Page 18

GROSS COOLING CAPACITIES (cont)580D102 (81⁄2TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacity

Page 19 - SPECIFICATIONS — 579F180-300

GROSS COOLING CAPACITIES (cont)580D150 (121⁄2TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacit

Page 20

GROSS COOLING CAPACITIES (cont)579F180 (15 TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95Cfm BFEwb(F)Capacity MBtuhCompressorkWCapacity

Page 21

GROSS COOLING CAPACITIES (cont)579F216 (18 TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95 105Cfm BFEwb(F)Capacity MBtuhCompressorkWCapac

Page 22 - GROSS COOLING CAPACITIES

<GROSS COOLING CAPACITIES (cont)579F240 (20 TON)Air EnteringEvaporatorAir Entering Condenser (F)75 85 95 105Cfm BFEwb(F)Capacity MBtuhCompressorkWC

Page 23

FACTORY-INSTALLED OPTIONS DESCRIPTION AND USAGEVarislide™ and Standard Integrated Economizer — Theeconomizer will allow a fixed percentage (between 0 a

Page 24

AIR DELIVERY — VERTICAL DISCHARGE UNITS580D036 (3 TON)Airflow(Cfm)Standard Direct Drive MotorLow Speed High Speed208 V 230, 460, 575 V 208 V 230, 460,

Page 25

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D048 (4 TON)Airflow(Cfm)Standard Direct Drive MotorLow Speed High Speed208 V 230, 460, 575 V 208 V 230

Page 26

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D060 (5 TON)Airflow(Cfm)Standard Direct Drive MotorLow Speed Medium Speed High Speed208 V 230, 460, 57

Page 27

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D072 (6 TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.1 0.2 0.4 0.6 0.8

Page 28

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D090 (71⁄2TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8 1.

Page 29

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D102 (81⁄2TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8 1.

Page 30

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D120 (10 TON)Airflow(Cfm)Standard and Alternate Belt Drive MotorsExternal Static Pressure (in. wg)0.2

Page 31

AIR DELIVERY — VERTICAL DISCHARGE UNITS (cont)580D150 (121⁄2TON)Airflow(Cfm)Standard and Alternate Belt Drive MotorsExternal Static Pressure (in. wg)0.

Page 32

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS580D036 (3 TON)Airflow(Cfm)Standard Direct Drive MotorLow Speed High Speed208 v 230, 460, 575 v 208 v 230, 460

Page 33

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D048 (4 TON)Airflow(Cfm)Standard Direct Drive MotorLow Speed High Speed208 v 230, 460, 575 v 208 v 2

Page 34

FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE (cont)LP (Liquid Propane) Kit (036-150) — Kit consists of gas ori-fices to convert the unit for use wit

Page 35

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D060 (5 TON)Airflow(Cfm)Standard Direct-Drive MotorLow Speed Medium Speed High Speed208 V 230, 460,

Page 36

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D072 (6 TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.1 0.2 0.4 0.6 0.

Page 37

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D090 (71⁄2TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8

Page 38

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D102 (81⁄2TON)Airflow(Cfm)Standard Belt Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8

Page 39

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D120 (10 TON)Airflow(Cfm)Standard and Alternate Belt Drive MotorsExternal Static Pressure (in. wg)0.

Page 40

AIR DELIVERY — HORIZONTAL DISCHARGE UNITS (cont)580D150 (121⁄2TON)Airflow(Cfm)Standard and Alternate Belt Drive MotorsExternal Static Pressure (in. wg)

Page 41

AIR DELIVERY — 579F180-300 UNITS579F180 (15 TON)Airflow(Cfm)Standard Belt-Drive Motor; 208/230-V and 460 V UnitsExternal Static Pressure (in. wg)0.2 0.

Page 42

AIR DELIVERY — 579F180-300 UNITS (cont)579F216 (18 TON)Airflow(Cfm)Standard Belt-Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8 1.0 1.2Rpm

Page 43

AIR DELIVERY — 579F180-300 UNITS (cont)579F300 (25 TON)Airflow(Cfm)Standard Belt-Drive MotorExternal Static Pressure (in. wg)0.2 0.4 0.6 0.8 0.9 1.0Rpm

Page 44

AIR QUANTITY LIMITSUNIT MINIMUM CFM MAXIMUM CFM580D036 900 1500580D048 1200 2000580D060 1500 2500580D072 1800 3000580D090 2250 3750580D102 2550 4250UN

Page 45

MODEL DESCRIPTION(ODS Model Number)HEATING CAPACITIES AND EFFICIENCIES, 036-150 UNITSUNIT 580DHEATING INPUT(Btuh)Stage 2/Stage 1OUTPUT CAPACITY(Btuh)T

Page 46

ACCESSORY/FIOP ECONOMIZER STATIC PRESSURE DROP (in. wg)UNITUNITVOLTAGECFMVARISLIDE™ECONOMIZERPRESSURE DROPPARABLADEECONOMIZERPRESSUREDROP580D036-072 A

Page 47

ELECTRICAL DATA — 580D036-150UNIT580DNOMINALVOLTAGE(60 Hz)IFMTYPEVOLTAGERANGECOMPR(ea)OFM(ea)IFMCOMBUSTIONFAN MOTORPOWER SUPPLYDISCONNECTSIZE*Min Max

Page 48

ELECTRICAL DATA — 579F180-300UNIT579FNOMINALVOLTAGE(60 Hz)VOLTAGERANGECOMPRESSOROFM IFMPOWEREXHAUSTCOMBUSTIONFAN MOTOR**POWER SUPPLYNO. 1 NO. 2Min Max

Page 49 - SOUND POWER (Total Unit)

OPERATING SEQUENCE (cont)When first-stage thermostat calls for heat, time-delay relay forevaporator fan begins timer sequence. Induced-draft relay clos

Page 50

TYPICAL WIRING SCHEMATIC — 580D036-150See Legend on page 57.54

Page 51 - ELECTRICAL DATA — 580D036-150

TYPICAL WIRING SCHEMATIC — 579F180-300See Legend on page 57.55

Page 52 - OPERATING SEQUENCE

TYPICAL INSTALLATION — 580D090-150Vertical Discharge DuctingNEC — National Electrical CodeHorizontal Discharge Ducting56

Page 53 - OPERATING SEQUENCE (cont)

TYPICAL INSTALLATION — 579F180-300LEGEND FOR TYPICAL WIRING SCHEMATICSNEC — National Electrical CodeNOTES:1. Illustration shown is a general guide onl

Page 54 - See Legend on page 57

APPLICATION DATA1. Ductwork (580D036-150) — Secure vertical dischargeductwork to roof curb. For horizontal discharge applica-tions, attach ductwork to

Page 55

APPLICATION DATA (cont)Concentric Duct Air Distribution(579F180-300 Only)NOTE: Do not drill in this area; damage to basepan may result inwater leak.Fa

Page 56 - Horizontal Discharge Ducting

CAPACITY RATINGSUNIT 580DNOMINALTONSSTANDARDCFMNET COOLINGCAPACITY (Btuh)TOTALkWSEER*EERSOUNDRATING(Bels)Belt Drive Direct Drive036 3 1200 35,000 4.0

Page 57

APPLICATION DATA (cont)EVAPORATOR-FAN MOTOR PERFORMANCEUNITEVAPORATOR-FANMOTORUNITVOLTAGEMAXIMUMACCEPTABLECONTINUOUSBHP*MAXIMUMACCEPTABLEOPERATINGWATT

Page 58 - OPTION AND ACCESSORY LIST

APPLICATION DATA (cont)ALTITUDE COMPENSATION* — 036-072 UNITSELEVATION(Ft)72,000 AND 115,000BTUH NOMINALINPUT150,000 BTUHNOMINAL INPUTNaturalGasOrifice

Page 59

APPLICATION DATA (cont)ALTITUDE COMPENSATION* — 090-150 UNITSELEVATION(Ft)125,000, 180,000,AND 224,000 BTUHNOMINAL INPUT250,000 BTUHNOMINAL INPUTNatur

Page 60 - APPLICATION DATA (cont)

ENGINEERS’ SPECIFICATION GUIDE — MODELS 580D036-150 (3 TO 121⁄2TONS)GENERAL: Furnish and install single-package, outdoor rooftop-mounted, electrically

Page 61

ENGINEERS’ SPECIFICATION GUIDE — MODELS 579F180-300 (15 TO 25 TONS)GENERAL: Furnish and install single-package, outdoor rooftop-mounted, electrically

Page 62

DIMENSIONAL DRAWING — 580D036-072UNIT580DSTANDARDUNITWEIGHTCORNERWEIGHT(A)CORNERWEIGHT(B)CORNERWEIGHT(C)CORNERWEIGHT(D)Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg03

Page 63

DIMENSIONAL DRAWING — 580D090-150UNIT580DSTANDARDUNITWEIGHTCORNERWEIGHT(A)CORNERWEIGHT(B)CORNERWEIGHT(C)CORNERWEIGHT(D)‘‘H’’ ‘‘J’’ ‘‘K’’ ‘‘L’’Lb Kg Lb

Page 64 - Air Conditioning

DIMENSIONAL DRAWING — 579F180,216UNIT579FCORNER WEIGHT*ABCDLb Kg Lb Kg Lb Kg Lb Kg180 231 348 158 360 163 373 169 523 237180 270 355 161 363 164 377 1