Bryant F Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Adoucisseurs Bryant F. Bryant F User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 85
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
580J*08--14D,F (2--COMPRESSOR)
NOMINAL 7.5 to 12.5 TONS
WITH PURONR (R--410A) REFRIGERANT
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 1....................
UNIT ARRANGEMENT AND ACCESS 2...........
SUPPLY FAN (BLOWER) SECTION 4..............
COOLING 6....................................
PURONR (R--410A) REFRIGERANT 8..............
COOLING CHARGING CHARTS 10................
CONVENIENCE OUTLETS 16....................
SMOKE DETECTORS 17.........................
PROTECTIVE DEVICES 24.......................
GAS HEATING SYSTEM 25......................
CONDENSER COIL SERVICE 35..................
RTU--MP CONTROL SYSTEM 35..................
ECONOMI$ER SYSTEMS 50......................
WIRING DIAGRAMS 59.........................
PRE--START--UP 62..............................
START--UP, GENERAL 62........................
START--UP, RTU--MP CONTROL 64................
OPERATING SEQUENCES 67.....................
FASTENER TORQUE VALUES 71.................
APPENDIX I. MODEL NUMBER SIGNIFICANCE 72.
APPENDIX II. PHYSICAL DATA 73................
APPENDIX III. FAN PERFORMANCE 75...........
APPENDIX IV. WIRING DIAGRAM LIST 82........
APPENDIX V. MOTORMASTER SENSOR
LOCATIONS 83.................................
UNIT ST ART-UP CHECKLIST 85..................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
compone nts. Only trained and qualified service personnel
should install, repair, or service air-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenc hing cloth for unbra zing operations.
Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operati ons. Have
fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. T his is the safety--alert
symbol
. When you see this symbol on t he unit and in
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert
symbol. DANGER identifies the most serious hazards
which will re sult in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Vue de la page 0
1 2 3 4 5 6 ... 84 85

Résumé du contenu

Page 1 - NOMINAL 7.5 to 12.5 TONS

580J*08--14D,F (2--COMPRESSOR)NOMINAL 7.5 to 12.5 TONSWITH PURONR (R--410A) REFRIGERANTService and Maintenance InstructionsTABLE OF CONTENTSSAFETY CON

Page 2 - UNIT ARRANGEMENT AND ACCESS

10COOLING CHARGING CHARTSC09221Fig. 10 -- Cooling Charging Charts (08D,F -- Both Circuits)580J

Page 3 - Seasonal Maintenance

11COOLING CHARGING CHARTSC09222Fig. 11 -- Cooling Charging Charts (12D,F -- Both Circuits)580J

Page 4 - SUPPLY FAN (BLOWER) SECTION

12COOLING CHARGING CHARTS12.5 TON CIRCUIT 1C09240Fig. 12 -- Cooling Charging Charts (14D,F -- Circuit 1)580J

Page 5

13COOLING CHARGING CHARTS12.5 TON CIRCUIT 2C09241Fig. 13 -- Cooling Charging Charts (14D,F -- Circuit 2)580J

Page 6 - Evaporator Coil

14Table 1 – Cooling Service AnalysisPROBLEM CAUSE REMEDYCompressor and CondenserFan Will Not Start.Power failure. Call power company.Fuse blown or cir

Page 7

15CompressorsLubricationCompressors are charged with the correct amount of oil atthe factory.UNIT DAMAGE HAZARDFailure to follow this caution may resu

Page 8 - PURONR (R--410A) REFRIGERANT

16CONVENIENCE OUTLETSELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personalinjury or death.Units with conveni ence outlet

Page 9 - (Part No. EC39EZ067)

17C08283UNITVOLTAGECONNECTASPRIMARYCONNECTIONSTRANSFORMERTERMINALS208,230240L1: RED +YELL2: BLU + GRAH1 + H3H2 + H4460 480L1: REDSplice BLU + YELL2: G

Page 10 - COOLING CHARGING CHARTS

18Duct smoke sensorcontrollerFastener(2X)Controller coverConduit nuts(supplied by installer)Conduit support plateCover gasket(ordering option)Conduit

Page 11

19Return Air Without EconomizerThe sampling tube is located across t he return air openingon the unit basepan. (See Fig. 22.) The holes in thesampling

Page 12 - 12.5 TON CIRCUIT 1

2FIRE, EXPLOSION HAZARDFailure to follow this warning could result inpersonal injury, death and/or property damage.Refer to the User’s Information Man

Page 13 - 12.5 TON CIRCUIT 2

20AEFCDBC08246Fig. 26 -- Typical Smoke Detector System WiringHighlightBSmoke detector NC contact set will open on smoke alarmcondition, de--energizing

Page 14

21Controller Alarm TestThe controller alarm test checks the controller ’s ability toinitiate and indicate an alarm state.OPERATIONAL TEST HAZARDFailur

Page 15 - 0.14 in +0.0/-0.03

22SD--TRK4 Remote Alarm Test Procedure1. Turn the key switch to the RESET/TEST position forseven seconds.2. Verify that the test/reset station’s Alarm

Page 16 - CONVENIENCE OUTLETS

23INDICATORSNormal StateThe smoke detector operates in the norma l state in theabsence of any trouble conditions and when its sensingchamber is free o

Page 17 - SMOKE DETECTORS

24Table 3 – Detector IndicatorsCONTROL OR INDICATOR DESCRIPTIONMagnetic test/reset switchResets the sensor when it is in the alarm or trouble state. A

Page 18 - Smoke Detector Locations

25Troubleshooting Supply Fan Motor Overload TripsThe supply fan used in 580J units is a forward--curvedcentrifugal wheel. At a constant wheel speed, t

Page 19 - Return Air

26Table 7 – Liquid Propane Supply Line Pressure RangesUNIT MODEL UNIT SIZE MIN MAX580J All11.0 in. wg(2740 Pa)13.0 in. wg(3240 Pa)Manifold pressure fo

Page 20 - Sensor and Controller Tests

27HEATER TUBEASSEMBLYSEAL STRIPS,SPONGE RUBBERREGULATORGASKETREGULATORRETAINERWIND CAPASSEMBLY(SHOWNINVERTED,AS SHIPPED)BURNER ASSEMBLYINDUCER FAN-MOT

Page 21 - 4 76--- 99% dirty

28MANIFOLD PRESSURE TAPGASVALVEBURNERSC09154Fig. 36 -- Burner Tray Details6. Remove igniter wires and sensor wires at the Integ-rated Gas Unit Control

Page 22 - Detector Cleaning

29125,000/90,000 BTUH INPUT180,000/120,000 BTUH INPUT240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUTC08447Fig. 38 -- Spark Adjustment (08--14)Bu

Page 23 - Test/reset

3BLOWERACCESSPANELCONTROL BOXCOMPRESSORSC09239Fig. 2 -- Typical Access Panel Location (Front)Routine MaintenanceThese items should be part of a routin

Page 24 - PROTECTIVE DEVICES

30C08240C08241580J08(D,F)150 onlyAll 580J*D,F except 150Fig. 39 -- Gas ValveOrifice ReplacementThis unit uses orifice type LH32RFnnn (where nnnindicat

Page 25 - Fuel Types and Pressures

31Red LED-StatusC08452Fig. 40 -- Integrated Gas Control (IGC) BoardTable 10 – IGC ConnectionsTERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF

Page 26 - Combustion--Air Blower

32Table 11 – Orifice SizesORIFICEDRILL SIZEBRYANTPART NUMBERDRILLDIA. (in.)#30 LH32RF129 0.12851/8 LH32RF125 0.1250#31 LH32RF120 0.1200#32 LH32RF116 0

Page 27 - Burners and Igniters

33Minimum Heating Entering Air TemperatureWhen operating on first stage heating, the minimumtemperature of air entering the dimpled heat exchanger is5

Page 28 - HOLE IN END PANEL (HIDDEN)

34Table 14 – IGC Board LED Alarm CodesLEDFLASHCODEDESCRIPTIONACTION TAKEN BYCONTROLRESET METHOD PROBABLE CAUSEOn Normal Operation — — —Off Hardware Fa

Page 29 - 250,000/200,000 BTUH INPUT

35CONDENSER COIL SERVICECondenser CoilThe condenser coil is new NOVAT ION Heat ExchangerTechnology. This is an all--aluminum construction withlouvere

Page 30 - Orifice Replacement

36C07129Fig. 42 -- RTU--MP Multi--Protocol Control Board580J

Page 31 - Red LED-Status

37C09163Fig. 43 -- Typical RTU--MP System Control Wiring Diagram580J

Page 32 - Table 11 – Orifice Sizes

38Table 15 – RTU--MP Controller Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBERSINPUTSSpace Temperature Sensor sptsens AI

Page 33

39Table 16 – Thermistor Resistance vs TemperatureValues for Space Temperature Sensor, Supply AirTemperature Sensor, and Outdoor Air TemperatureSensorT

Page 34

422 3/8 (569 mm)HOODDIVIDEROUTSIDEAIRCLEANABLEALUMINUMFILTERBAROMETRICRELIEFFILTERCAPFILTERC08634Fig. 3 -- Filter InstallationTo remove the filter, op

Page 35 - RTU--MP CONTROL SYSTEM

40SENSENJ20-1J20-2C08460Fig. 46 -- RTU--MP T--55 Sensor ConnectionsConnectT-- 56See Fig. 47 for T--56 internal connections. Install a jumperbetween SE

Page 36

41The enthalpy c ontrol receives the outdoor ai r enthalpyfrom the outdoor air enthalpy sensor and provides a dryconta ct switch input to the RTU--MP

Page 37

42To connect the sensor to the control, identify the positive(4 to 20 mA) and ground (SIG COM) terminals on thesensor. (See Fig. 52.) Connect the 4--2

Page 38

43Remote OccupancyThe remote occupancy accessory is a field --installedaccessory. This accessory overrides the unoccupied modeand puts the unit in occ

Page 39 - EconoMi$er 2

44SW3 Protocol SelectionPROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1BACnet MS/TP(Master)Unused OFF OFF OFF ON OFF Select Baud Select BaudModbus(Slave)Unus

Page 40 - Economizer Controls

45Table 17 – LEDsThe LEDs on the RTU--MP show the status of certain functionsIf this LED is on... Status is...Power The RTU MP has powerRx The RTU MP

Page 41

46Table 18 – Troubleshooting AlarmsPOINT NAMEBACnetOBJECTNAMEACTION TAKEN BYCONTROLRESETMETHODPROBABLE CAUSESafety Chain Alarm safety_chainAlarm Gener

Page 42 - Connecting Discrete Inputs

47AlarmsAlarms can be checked through the network and/or thelocal access. All the alarms are listed in Table 18 withname , object name, action taken b

Page 43 - Power Exhaust (output)

48Device Instance: 0160001 1 PRGs loaded. 1 PRGs running. Module status: Firmware sections validated in flash memory ================================

Page 44 - RTU-- MP Troubleshooting

49Table 19 – Manufacture DateWhen troubleshooti ng, you may need to know a control module’s manufacture dat eObtain the manufacture date froma...Notes

Page 45 - Table 17 – LEDs

5To replace the belt:1. Use a belt with same section type or similar size. Donot substitute a “FHP” type belt. When installing thenew belt, do not use

Page 46

50NOTE: See RTU--MP 3rd Party Int egration Guide (oralternatively RTU --MP 3rd Party Integration Guide (oralternatively RTU--MP Controls, Start--Up, O

Page 47 - BACnet MS/TP

51C09023Fig. 62 -- EconoMi$er IV Wiring435286711011912PINKVIOLETBLACKBLUEYELLOWNOTE 1NOTE 3RUN500 OHMRESISTOR50HJ540573ACTUATORASSEMBLYREDWHITEECONOMI

Page 48

52Table 22 – EconoMi$er IV Input/Output LogicINPUTS OUTPUTSDemand ControlVentilation (DCV)Enthalpy*Y1 Y2Compressor NTerminal†Outdoor ReturnStage1Stage

Page 49

53Supply Air Temperature (SAT) SensorThe supply air temperature sensor is a 3 K thermistorlocated at the inlet of the indoor fan. (See Fig. 65.) Thiss

Page 50 - ECONOMI$ER SYSTEMS

54Differential Dry Bulb ControlFor differential dry bulb control t he standard outdoor drybulb sensor is used in conjunction with a n additionalaccess

Page 51

55TR124 VacCOMTR24 Va cHOT12345EFEF1+_P1T1PTNEXH2V 10VEXHSetSet2V 10V2V 10VDCVDCVFreeCoolBCADSO+SR+SRSOAQ1AQDCVMinPosOpenMaxN1C06038Fig. 71 -- EconoMi

Page 52 - EconoMi$er IV

56Adjust the minimum position potentiometer to allow theminimum amount of outdoor air, as required by localcodes, to enter the building. Make minimum

Page 53

57The same equation can be used to determine the occupiedor maximum ventilation rate to the building. For example,an out put of 3.6 volts to the actua

Page 54 - HIGH LIMIT

58Table 24 – EconoMi$er IV Sensor UsageAPPLICATIONECONOMI$ER IV WITH OUTDOOR AIR DRYBULB SENSORAccessories RequiredOutdoor AirDry BulbNone. The outdoo

Page 55 - RANGE CONFIGURATION (ppm)

595. Turn the DCV setpoint potentiometer CW until theDCV LED turns off. The DCV LED should turn offwhen the potentiometer is approximately 9--v. Theac

Page 56

6Changing the Fan Wheel Speed by Changing PulleysThe horsepower rating of the belt is primaril y dictated bythe pitch diameter of the smaller pulley i

Page 57

60C09156Fig. 73 -- 580J Typical Unit Wiring Diagram -- Power (08D,F, 208/230--3--60)580J

Page 58

61C09157Fig. 74 -- 580J Typical Unit Wiring Diagram -- Control (08--12D,F, 208/230--3--60)580J

Page 59 - WIRING DIAGRAMS

62PRE--START-- UPPERSONAL INJUR Y HAZARDFailure to follow this warning could result in personalinjury or death.1. Follow recognized safety practic es

Page 60

63UNIT OPERATION AND SAFETY HAZARDFailure to follow this warning could result in personalinjury or death.Disconnect gas piping from unit when leak tes

Page 61

64NOTE: The default value for the evaporator--fan m otoron/off delay is 45 seconds. The Integrated Gas UnitController (IGC) modifies this value when a

Page 62 - START--UP, GENERAL

65Filter Service HoursThis refers to the timer set for the Dirty Filter Alarm.After the number of runtime hours set on this point isexceeded the corre

Page 63

66Input 5This input is a discrete input and can be configured to beone of five different inputs: No Function, Fire Shutdown,Fan Status, Filter Status,

Page 64 - START--UP, RTU--MP CONTROL

67Power Exhaust SetptWhen the economizer damper position opens above thispoint t he power exhaust operation will begin. When thedamper position falls

Page 65

68When free cooling is available as determined by theappropria te changeover command (dry bulb, outdoorenthalpy, differential dry bulb or differential

Page 66 - the current

69SchedulingScheduling is used to start heating or cooling (becomeoccupied) based upon a day of week and a time period andcontrol to the occ upied hea

Page 67 - OPERATING SEQUENCES

7Routine Cleaning of NOVATION Condenser CoilSurfacesTo clean the NOVATION condenser coil, chemicals areNOT to be used; only water is approved as the c

Page 68 - RTU--MP Sequence of Operation

70CoolingThe compressor out puts are controlled by the CoolingControl PID Loop and Cooling Stages Capacity algorithm.They will be used to calculate th

Page 69

71Indoor Air QualityIf the optional indoor air quality sensor is installed, theRTU --MP will maintain indoor air quality within the spaceat the user c

Page 70 - The indoor fan will be

72APPENDIX I. MODEL NUMBER SIGNIFICANCEModel Number Nomenclature1234567891011121314151617185 8 0 J E 0 8 D 1 2 5 A 1 A 0 A A --____________ ______ ___

Page 71 - FASTENER TORQUE VALUES

73APPENDIX II. PHYSICAL DATAPhysical Data (Cooling) 7.5 -- 12.5TONS580J*08D,F 580J*12D,F 580J*14D,FRefrigeration System#Circuits/#Comp./Type 2/2/Scrol

Page 72 - Serial Number Format

74APPENDIX II. PHYSICAL DATA (cont.)Physical Data (Heating) 7.5 -- 12.5TONS580J**08 580J**12 580J**14Gas C onnection#ofGasValves 1 1 1Nat. gas supply

Page 73 - APPENDIX II. PHYSICAL DATA

75APPENDIX III. FAN PERFORMANCE580J**08 3 PHASE 7.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP R

Page 74

76FAN PERFORMANCE (cont.)580J**12 3 PHASE 10 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(in.wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 75 - APPENDIX III. FAN PERFORMANCE

77580J**14 3 PHASE 12.5 TON HORIZONTAL SUPPLYCFMAvailable External Static Pressure (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPS

Page 76 - FAN PERFORMANCE (cont.)

78580J**14 3 PHASE 12.5 TON VERTICAL SUPPLYCFMAvailable External Static Pressure (in. wg)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPSta

Page 77

79APPENDIX III. FAN PERFORMANCE (cont.)Pulley AdjustmentUNITMOTOR/DRIVECOMBOMOTOR PULLEY TURNS OPEN0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0083phase

Page 78

89. Finned surfaces should remain wet with cleaningsolution for 10 minutes.10. Ensure surfaces are not allowed to dry before rinsing.Reapply cleaner a

Page 79 - Pulley Adjustment

80ELECTRICAL INFORMATION580J*08D,F 2---Stage Cooling 7.5 TonsV --- P h --- H zVOLTAGERANGECOMP (Cir 1) COMP (Cir 2) OFM (ea) IFMRLA LRA RLA LRA WATTS

Page 80 - ELECTRICAL INFORMATION

81MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.UNITNOM.V --- P h --- H zIFMTYPECOMBUSTIONFAN MOTORFLAPOWEREXHAUSTFLANO C.O. or UNPWRD C.O.NO P.E. w/ P

Page 81

82APPENDIX IV. WIRING DIAGRAM LISTWiring Diagrams580JSIZE VOLTAGE CONTROL POWER08D,F208/230--- 3 ---60 48TM501325 48TM501326460--- 3 ---60 48TM501325

Page 82 - Wiring Diagrams

83APPENDIX V. MOTORMASTER SENSOR LOCATIONS580/558J-D08580/558J-D12C09226Fig. 75 -- 580J*08--12D,F Outdoor CircuitingNOTE: The low ambient kit for the

Page 84

85UNIT START-UP CHECKLISTI. PRELIMINARY INFORMATION:MODEL NO.:DATE: ______________SERIAL NO: _____________________________________TECHNICIAN: ________

Page 85 - UNIT START-UP CHECKLIST

91/2-20 UNF RH300.596.475/8” HEXSEATCORE WASHERDEPRESSOR PER ARI 720+.01/-.035 FROM FACE OF BODY7/16-20 UNF RHO-RING45torqued into the seat. Appropri

Modèles reliés 580J*08--14D

Commentaires sur ces manuels

Pas de commentaire